Specifications
Humidity
- 5 to 90 % RH, Non-Condensing
Insulation Resistance
- 100 MΩ at 500 Vdc between Input & Output, Output & Power Supply, & Input & Power Supply
Mounting
- DIN Rail Mounting
- Rack-Mounted
- Wall Mounted
Operating Temperature
- 0° to 50° C (32° to 122° F)
Power Supply Effect
- ± 0.1 % of Span or Less for the Fluctuations within the Operating Range of Power Supply Voltage Specification
Resistance
- 1 MΩ (100 kΩ During Power Off) - Input Resistance
- 300 ohms or Less (10 to 50 mA DC Outputs)
- 750 ohms or Less (4-20 mA DC Outputs) - Allowable Load Resistance
Response Time
- 150 ms, 63 % Response (10 to 90 %)
Span & Zero Adjustments
- -1 to 1 % - Zero Adjustment
- 95 to 105 % - Span Adjustment
Supply Voltage
- 1,500 Vac/minute between (Input & Power Supply) & Output
- 500 Vac/minute between Input & Power Supply
Temperature Effect
- ± 0.2 % of Span or Less for a Temperature Change of 10° C (18° F)