Specifications
Accuracy
- ± 0.3 % of Span
- Relative Error between Output 1 & 2 is within ± 0.2 %
Consumption
- 6 VA at 100 Vac - Power Consumption (WG3V-2)
- 60 mA at 24 Vdc - Current Consumption (WG3V-1)
- 7 VA at 100 Vac - Power Consumption (WG3A-2)
- 90 mA at 24 Vdc - Current Consumption (WG3A-1)
Frequency
- 40 to 1,000 Hz - Input Frequency
Humidity
- 5 to 90 % RH, Non-Condensing
Input
- 120 % (Continuous) - Max.
- 200 % (One Minute) - Max.
Input Signal
- 0.1-150 Vac - Span
- 0 to 150 Vac
Insulation Resistance
- 100 MΩ or more at 500 Vdc
Mounting
- DIN Rail Mounting
- Rack-Mounted
- Wall Mounted
Operating Temperature
- 0° to 50° C (32° to 122° F)
Output
- 0-24 mA DC
- 10 mV to 20 V - Span (DC)
- -10 to 10 Vdc
- 1-24 mA - Span (DC)
Power Supply
- 24 Vdc ± 10 %
- 85-264 Vac, 47 to 63 Hz
Power Supply Effect
- ± 0.1 % of Span or Less for Fluctuation within the Operating Range of Power Supply Voltage Specification
Resistance
- 2 to 250 kΩ - DC Voltage Allowable Load Resistance
- 750 to 15,000 ohms - DC Current Allowable Load Resistance
- Approximately 1 MΩ - Input Resistance
Response Time
- 300 ms, 63 % Response (10 to 90 %)
Span & Zero Adjustments
- -5 to 5 % - Zero Adjustment
- 95 to 105 % - Span Adjustment
Supply Voltage
- 1,500 Vac/minute - AC & DC Drive Withstand Voltage
- 500 Vac/minute - DC Drive Withstand Voltage
Temperature Effect
- ± 0.2 % of Span or Less for a Temperature Change of 10° C (18° F) - Effect of Ambient Temperature Change
Zero Offset
- 0 to 200 % - Zero Elevation (Current Signal)
- -100 to 200 % - Zero Elevation (Voltage Signal)