± 1° C (± 1.8° F) - Reference Junction Compensation Accuracy (Typical K, J, T, E, B, N, W3 & W5)
± 2° C (± 3.6° F) - Reference Junction Compensation Accuracy (Typical R, S) at 25° C (77° F) ± 15° C (27° F)
Alarm
0 to 100 % of Input Range - Alarm Setting Range
Upper & Lower Limit Alarms - Direction of Alarm Action
Burn-Out
60 seconds - Burn-Out Time
Down
Off
Up
Consumption
1.9 W at 24 Vdc, 110 Vdc - Power Consumption
4.1 VA at 100 Vac - Power Consumption
5.1 VA at 200 Vac - Power Consumption
Current
0.05 µA - Burn-Out Detective Current
Electrical Connectors
M3 Screw Terminal
Electrical Rating
0.1 A at 120 Vdc - Resistive Load
0.5 A at 220 Vac - Resistive Load
1 A at 120 Vac
1 A at 30 Vdc
Enclosure, Body Material
Modified Polyphenylene Oxide Resin
Humidity
5 to 90 % RH, Non-Condensing - Operating Humidity
Hysteresis
0 to 100 % of Input Range - Hysteresis Setting Range
3 % of Input Range (Alarm 1 & Alarm 2)
Indication
LED - Front Panel Lights
Insulation Resistance
100 MΩ at 500 Vdc between Input, Output 1, Output 2, Power Supply & Grounding Terminals Mutually
Measuring Span
3 mV or more (Converted Into Thermoelectromotive Force)
Mounting
DIN Rail Mounting
VJ Mounting Base
Wall Mounted
Operating Temperature
0° to 50° C (32° to 122° F)
Output Format
Relay Contact
Output Function
NO Contact Output
Power Supply
100-240 Vac/dc (-15 %, 10 %), 50/60 Hz
15-30 Vdc (± 20 %)
Power Supply Effect
± 0.1 % of Span or Less for the Fluctuations within the Allowable Range of Each Power Supply Voltage Specification - Effect of Power Supply Voltage Fluctuations
Relay Operation
Energized or De-Energized Under Normal Condition - Direction of Relay Action
Resistance
1 MΩ (During Power-On) - Input Resistance
4 kΩ (During Power Off) - Input Resistance
500 ohms or Less - Allowable Leadwire Resistance
Resolution
0.1 % - Alarm & Hysteresis Setting Resolution
0.1° C, with Four Significant Digits - Setting Resolution
1 second (However, about 0.2 second is to be added to the set time to prevent wrong operation) - Alarm ON & OFF setting resolution
Response Time
450 ms (Time to Alarm Output when the Input Change is 10 to 90 % & Alarm Set Point is 50 %. when the Alarm Delay Setting & Hysteresis are min.)
Sensor, Probe Type
B Thermocouple (RH)
E Thermocouple (CRC)
J Thermocouple (IC)
K Thermocouple (CA)
N Thermocouple
R Thermocouple
S Thermocouple
T Thermocouple (CC)
W3 Thermocouple
W5 Thermocouple
Supply Voltage
± 4 Vdc - Max.
1,000 Vac/minute between Output 1 & Output 2 Termianls - Withstand Voltage
2,000 Vac/minute between Input, (Output 1, Output 2), Power Supply & Grounding Terminals Mutually - Withstand Voltage
Temperature Effect
± 0.2 % of Span or Less for a Temperature Change of 10° C (18° F) - Effect of Ambient Temperature Change
Temperature Range
0° to 1,000° C (32° to 1,832° F) - Input Range
-200° to 2,000° C (-328° to 3,632° F) - Guaranteed Range
Update Time
0 to 999 seconds - Alarm ON & OFF Delay Setting Range