Voltage & Power Range
- Mains: 3-Phase, U N 380-480 V, +10 %/-15 % from 0.75 to 22 kW
- Motor: 0 to UN, 3-Phase
Frequency
- Motor: 0 to 599 Hz
- Mains: 48 to 63 Hz
Storage / Transport Temperature
Humidity
- 5 % to 95 % RH, No Condensation
Power Supply
- External: 1.04 A at 24 Vac/dc ± 10 % as option
Communication
- External 2-Port option: EtherNet Adapter for remote Monitoring.
- Plug-In option: CANopen, DeviceNet, PROFIBUS DP
- 2-Port plug-in option: BACnet/IP, Modbus TCP, PROFINET IO, EtherNet/IP, EtherCAT, EtherNet POWERLINK
- Standard: BACnet MS/TP, Modbus RTU and N2
Certifications & Approvals
- WEEE
- RoHS
- EMC
- LVD
- CE
- UL, EAC, RCM, cUL
- TÜV Nord
Altitude
- 0 to 1,000 m
- Reduced by 1 % per 100 m 1,000 to 4,000 m
Input & Output
- 2 analog Input/output
- 6 Digital Input
- 3 Relay output