Specifications
Accuracy
- ± 0.1 % of Span - Output 1
- Within ± 0.2 % - Relative Error between Output-1 & 2
Consumption
- 50 mA at 24 Vdc (1-5 V) - Current Consumption
- 75 mA at 24 Vdc (4-20 mA) - Current Consumption
Current
- 0.1 µA - Burn-Out Detective Current
- 1-24 mA DC - Span
Electrical Connectors
- M4 Screw Terminal of the Dedicated Nest - External Wiring
Humidity
- 5 to 90 % Reltive Humidity, Non-Condensing
Insulation Resistance
- 100 MΩ or more at 500 Vdc between Input & Output, Output & Power Supply, & Input & Power Supply
Operating Temperature
- 0° to 50° C (32° to 122° F)
Output
- 0-100 mVdc
- 0-24 mA DC
- 10 mV - 20 V - Span (DC)
- -10 to 10 Vdc
Power Supply
- 24 Vdc ± 10 % (Ripple Content 5 % Peak-to-Peak or Less)
Power Supply Effect
- ± 0.1 % of Span or Less for the Fluctuation within the Operating Range of Power Supply Voltage - Effect of Power Supply Voltage Fluctuations
Resistance
- 100 to 2,000 ohms - Total Resistance
- 150 ohms or Less Per Wire - Allowable Leadwire Resistance
- 80 to 2,000 ohms - Measuring Span (50 % of the Total Resistance or more)
- More Than 2 to 30 kΩ - Total Resistance
Response Time
- 200 ms, 63 % Response (10 to 90 %)
Span & Zero Adjustments
- ± 10 % of Span - Output Adjustment
Supply Voltage
- 1,500 Vac/minute between Input & (Output & Power Supply) - Withstand Voltage
- 500 Vac/minute between Output & Power Supply - Withstand Voltage
Temperature Effect
- ± 0.2 % of Span or Less for a Temperature Change of 10° C (18° F) - Effect of Ambient Temperature
Zero Offset
- 0 to 200 % - Zero Elevation (Current Signal)
- -100 to 200 % - Zero Elevation (Voltage Signal)
- 50 % or Less of the Total Resistance