Adjustment Type
- Factory Set (Pre-Set)
- Field Adjustable
Approvals & Certifications
Electrical Contacts
- Normally Closed
- Normally Open
Electrical Rating
- Inductive: 1 A at 110 Vac, 0.5 A at 220 Vac, 0.5 A at 24 Vdc (De-Rate 70 % to 80 % for Every Slow Pressure Changes)
- 2.5 A at 110 Vac, 1.5 A at 220 Vac, 1 A at 24 Vdc, 0.5 A at 110 Vac
Operating Temperature
- -34° for Dry Air or Gas to 43° C (-30° to 110° F)
Proof Pressure
- bar: 1.7
- kPa: 172.37
- psig: 25
Set Point - Decreasing
- inH₂O: 0.01 to 12
- kPa: 0.005 to 3
Set Point - Increasing
- inH₂O: 0.01 to 12
- kPa: 0.005 to 3
System Pressure
- bar: 0.68
- kPa: 68.95
- psig: 10