VJA1 Isolated Single & Dual Output Distributor

Brand: Yokogawa Electric Corporation

VJA1 Isolated Single & Dual Output Distributor

Brand: Yokogawa Electric Corporation
The VJA1 is a compact, plug-in type distributor that is used in combination with a two-wire type transmitter to convert the transmitter’s 4-20 mA DC signals into isolated DC current or DC voltage signals.
Features
  • HART communication: VJA1/H (option code /H) Bi-directional relay of HART communication signals is possible while the field devices and the higher-level device are isolated from each other.
  • Supports BARD-800.

Specifications

Accuracy

  • ± 0.1 % of Span

Approvals & Certifications

  • CE
  • EMC EN 61326

Consumption

  • 3.1 W at 110 Vdc - Power Consumption
  • 3.2 W at 24 Vdc - Power Consumption
  • 6.1 VA at 100 Vac - Power Consumption
  • 8.3 VA at 200 Vac - Power Consumption

Current

  • 1-24 mA DC - Span
  • 25-35 mA - Current Limiter

Electrical Connectors

  • M3 Screw Terminal

Electrical Contacts

  • Normally Closed - Output-2

Enclosure, Body Material

  • Modified Polyphenylene Oxide

Environmental Protection

  • Intrinsically Safe

Humidity

  • 5 to 90 % RH, Non-Condensing - Operating Humidity

Input

  • 40 mA DC - Max.

Input Signal

  • 4-20 mA DC Signal from 2-Wire Typical Transmitter

Insulation Resistance

  • 100 MΩ min. at 500 Vdc between Input, Output-1, Output-2, Power Supply & Grounding Terminals Mutually

Mounting

  • Base Mounting (VJCE) - VJ Mounting
  • DIN Rail Mounting
  • Wall Mounted

Operating Temperature

  • 0° to 50° C (32° to 122° F)

Operating Voltages

  • 12-36 V
  • 85-264 V

Output

  • 0-100 mVdc
  • 0-24 mA DC
  • -10 to 10 Vdc
  • 1-5 Vdc
  • 4-20 mA DC

Power Supply

  • 100-240 Vac/dc (-15 %, 10 %) 50/60 Hz (Operating Range: 85-264 V) - Supply Input & Rated Voltage Range
  • 15-30 Vdc (± 20 %) (Operating Range: 12-36 V) - Supply Input & Rated Voltage Range
  • 25.25 ± 0.25 Vdc (Provided with a Current Limiter to Keep the Current between 25-35 mA) - Transmitter Power Supply

Power Supply Effect

  • Up to ± 0.1 % of Span for the Regulation within Allowable Range of Each Supply Voltage Range - Effects of Power Line Regulation

Resistance

  • 250 ohms - Input Resistance
  • 350 to 250,000 ohms - Allowable Load Resistance

Response Time

  • 150 ms, 63 % Response (10 to 90 %)

Span & Zero Adjustments

  • -5 to 5 % - Zero Adjustment
  • 95 to 105 % - Span Adjustment

Supply Voltage

  • 1,000 Vac for One Minute between Output-1 & Output-2 Terminals - Withstanding Voltage
  • 10 mV-20 V - Span (DC)
  • 2,000 Vac for One Minute between Input, Output-1 & Output-2, Power Supply & Grounding Terminals - Withstanding Voltage

Temperature Effect

  • Up to ± 0.15 % of Span Per 10° C (18° F) - Effects of Ambient Temperature Variations

Version / Leadwires

  • 2-Wire Typical Transmitter

Zero Offset

  • 0 to 200 % - Zero Elevation for Current Signal
  • -100 to 200 % - Zero Elevation for Voltage Signal

Documentation

show more